Temperature Transmitters

Product Details · PRODUCT DETAILS

LU-GSZ Intelligent RTD Temperature Transmitter

The LU-GSZ intelligent RTD temperature transmitter is used in automation control for industrial signal transmission, conversion, isolation and computation. It works with various industrial sensors to acquire signals and transmits them after isolation, meeting local monitoring and remote data acquisition needs.

  • CategoryTemperature Transmitters
  • Model-
  • Views6608 views
  • Updated2026-03-09
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111

I. Overview

The LU-GSZ smart RTD temperature transmitter is an instrument for industrial signal transmission, conversion, isolation, and computation in automation control. It can be used with various industrial sensors to acquire signals and transmit them after isolation, meeting the needs of local monitoring and remote data acquisition.
It is widely used for data acquisition and signal transmission and conversion in industries such as semiconductors, photovoltaics, new energy, machinery, electrical, telecommunications, power, petroleum, chemical, steel, wastewater treatment, and building construction, as well as in industrial measurement and control systems such as PLC\DCS, where it complements and extends the system's analog I/O module functions and improves system applicability and on-site reliability. 

II. Technical Parameters

(I) Input Parameters

Type Measuring range (°C) Minimum span (°C)
Cu50 -50-150 50
Cu100 -50-150 50
Pt10 -200-600 200
Pt100 -200-800 50

(II) Output Parameters

  1. Current output: 4-20mA (uses isolator power supply), allowable load ≤500Ω
  2. Voltage output: 1-5V, allowable load ≥10KΩ

(III) Environmental Parameters

 
  1. Power supply: DC24V±10%, ripple factor below 10% P-P, power consumption approx. 2W
  2. Operating temperature range: -5~+55°C
  3. Operating humidity range: 0~90% RH (non-condensing)
  4. Power indicator: red LED, lit steadily when powered

(IV) Performance Specifications (relative to full scale)

  1. Standard accuracy: ±0.3%
  2. Temperature coefficient: ±0.015%/°C
  3. Response time: ≤0.5S (0→90%)
  4. Effect of power supply voltage variation: ±0.1%/ allowable voltage range
  5. Insulation resistance: between input — output — power supply, 100MΩ or more / DC 500V
  6. Isolation strength: between input - output - power supply - ground, DC 1500V for 1 minute (DC power), AC 1500V for 1 minute (AC power)
  7. Effect of load resistance variation: ±0.1%/250Ω
  8. Power-on stabilization time: ≤3s
 

III. Selection Guide

 

Basic Model Classification

  • LU-GSZ11×××: one input, one output
  • LU-GSZ12×××××: one input, two outputs
  • LU-GSZ22×××××: two inputs, two outputs
 

LU-GSZ Intelligent RTD Temperature Transmitter User Manual

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS

Related Products

View Related Products

Need technical specifications and a quotation for this product?

Submit your request and our engineers will contact you within one business day.