Temperature Transmitters
Product Details · PRODUCT DETAILS
LU-GCL12 One-In Two-Out Intelligent Transmitter
The LU-GCL12 one-in two-out intelligent transmitter is a high-performance, highly reliable intelligent industrial controller built on an entirely new design concept. It is widely used in automatic temperature, flow, pressure and level control systems in the semiconductor, photovoltaic, chemical, ceramics, metallurgy, petrochemical and heat treatment industries.
I. Overview
The LU-GCL12 one-input two-output smart transmitter is a high-performance, high-reliability intelligent industrial controller built on an entirely new design concept. It is widely used in automatic control systems for temperature, flow, pressure and level in the semiconductor/photovoltaic, chemical, ceramics, metallurgy, petrochemical and heat treatment industries.
Main features:
Equipped with an advanced ARM processor, it offers fast processing speed, simple interface circuitry, and high reliability and stability.
It covers signals from thermocouples and RTDs of all common graduation types as well as standard voltage and standard current signals; the fast and accurate nonlinear correction algorithm ensures the accuracy of digital sampling.
It provides a standard analog transmitter output function, with the transmitter type and transmitter range freely configurable.
Dual-row 4-digit LED display for simple and easy human-machine operation; the input signal type can be switched freely.
Excellent immunity to interference; complies with the industrial level-3 EMC test requirements.
2. Main Technical Specifications
Input specifications and range:
Thermocouple: S (-50~1768), R (-50~1768), B (250~1820), K (-200~1372), N (-200~1300), E (-200~1000), J (-200~1200), T (-200~400)
RTD: PT100 (-200~800), Cu50 (-50~150), Cu100 (-50~150)
Standard millivolt signal: custom 0~100mV
Standard resistance signal: custom 0~500 ohm
Standard voltage signal: 0~10V, 0~5V, 1~5V, custom 0~10V
Standard current signal: 4~20mA, 0~10mA, custom 0~20mA
Other technical parameters:
Measurement accuracy: class 0.2 (±0.2% FS ±1 digit)
Cold junction compensation: ±1°C
Sampling resolution: 1°C or 0.1°C
Sampling period: 0.5 s
Open thermocouple/open RTD and over-range detection: displays 5b
Output modes: 0~10mA current output (load capability < 1000 ohm), 4~20mA current output (load capability < 500 ohm), 0~20mA current output (load capability < 500 ohm)
Power supply: 20-35VDC / 85~265VAC
Overall power consumption: less than 4W
Operating environment: temperature -10~+60°C, humidity 0~80%RH
LU-GCL12 One-In Two-Out Intelligent Transmitter User Manual
Click to download the product manual. If the download fails, please contact customer service.
Related Products
Need technical specifications and a quotation for this product?
Submit your request and our engineers will contact you within one business day.