Isolators / Distributors

Product Details · PRODUCT DETAILS

LU-GSR Intelligent Thermocouple Signal Isolation Processor

Converts thermocouple signals into isolated standard process signals that are linear with temperature. Features include magnetic isolation between input, output and power supply, fully digital adjustment, a power indicator, and card-mounted construction. Automatic cold junction compensation is provided for K, E, S and other thermocouple types.

  • CategoryIsolators / Distributors
  • Model-
  • Views5504 views
  • Updated2011-11-25
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111
I. Overview

● Converts thermocouple signals into isolated standard process signals linear with temperature

● The input, output and power supply are magnetically isolated from one another

● Fully digital adjustment

● With power indicator lamp

● Card-mount signal isolation processor

II. Technical specifications

● Input parameters

Input range (automatic cold junction compensation)

 Graduation     Measuring range    Minimum span

K          0-1300        120 

E          0-1000         80 

S          0-1600        580 

B         400-1800      1000

R          0-1600        850

T         -200-400       120

N          0-1200        180

Wre325     0-2300        340

J           0-800         100

● Output parameters

For current output  

Output range: 4~20mA (using the isolator power supply )

           4~20mA (external 24VDC power supply )

             Permissible load: ≤500Ω

For voltage output  Output range: 1~5V  

             Permissible load: ≥10KΩ

● Ambient parameters

Power sup ply: DC24V±10% 

 Ripple factor below 10%P-P, approx. 2W  

Operating temperature range: -5 ~ +55 °C

Operating humidity range: 0~90%RH (non-condensing)

Power indicator lamp: red LED, lit when the power is supplied

● General technical parameters

Standard accuracy: ±0.3%

Temperature coefficient: ±0.015%/°C

Response time: ≤0.5S (0→90%)

Effect of power supply voltage variation: ±0.1%/permissible voltage range

Insulation resistance: between input—output—power supply

          100MΩ or more/DC 500V

Isolation strength: between input-output-power supply- ground

          DC 1500V  1 minute (DC power supply)

          AC 1500V  1 minute (AC power supply)

Effect of load resistance variation: ±0.1%/250Ω

Power-on stabilization time: ≤3s 

 

LU-GSR Intelligent Thermocouple Signal Isolation Processor User Manual

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS

Related Products

View Related Products

Need technical specifications and a quotation for this product?

Submit your request and our engineers will contact you within one business day.