Safety Barriers

Product Details · PRODUCT DETAILS

LU-A22 Detection-End (Signal Input) Isolation Safety Barrier (2 In / 2 Out)

The LU-A22 safety barrier supplies power to field transmitters, limits hazardous energy from entering the hazardous area through the intrinsically safe terminals, and converts DC signals into isolated standard process signals. It can connect two independent two-wire transmitters, with two independent input and output channels, each magnetically isolated between input, output and power supply.

  • CategorySafety Barriers
  • Model-
  • Views5247 views
  • Updated2011-11-25
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111

I. Overview

● The LU-A22 safety barrier supplies power to field transmitters, limits hazardous energy from entering the hazardous location through the intrinsically safe terminals, and converts DC signals into isolated standard process signals.

● Can be connected to two independent two-wire transmitters.

● Two independent input and output channels; for each channel, the input, output and power supply are magnetically isolated from one another.

II. Technical specifications

●Input parameters (hazardous area signals)

For current input  Input range: 4~20mA, 0-20mA, 0-10mA

Distribution voltage: ≥16VDC

Output resistance: built-in input resistor 100Ω

For voltage input  Input range: 1~5V, 0~5V, 0~10V

Input impedance: ≥500KΩ

Thermocouple input (millivolt signal), input range:

Graduation

Measuring range (°C)

Minimum span (°C)

K

0-1300

120

E

0-1000

80

S

0-1600

580

B

400-1800

1000

R

0-1600

850

T

-200-400

120

N

0-1200

180

W

0-2300

340

J

0-1200

100

  

Minimum millivolt span: 3mV

RTD input, input range:

Graduation

Measuring range (°C)

Minimum span (°C)

Cu50

-50-150

50

Cu100

-50-150

50

Pt10

-200-600

200

Pt100

-200-800

50

Permissible lead resistance : ≤5Ω (identical for the three wires)

●Output parameters (safe area signals)

For current output  Output range: 4~20mA, 0-20mA, 0-10mA

Permissible load: ≤350Ω

For voltage output  Output range: 1~5V, 0~5V, 0~10V

Output impedance: ≤500Ω

●Intrinsic safety parameters

Linear current/voltage                      Thermocouple/RTD

Explosion-proof marking: [Exia] ⅡC           Explosion-proof marking: [Exia] ⅡC

  Maximum permissible voltage Um: 250V         Maximum permissible voltage Um: 250V

  Maximum output voltage Uo: 28V           Maximum output voltage Uo: 12V

Maximum output current Io: 93mA          Maximum output current Io: 24mA

● Ambient parameters

Power sup ply: 20-30VDC

Ripple factor below 10%P-P, approx. 1W 

Power indicator lamp: green LED, lit when the power is supplied

Operating temperature range: -20~ +60°C

Operating humidity range: 0 ~ 95%RH (non-condensing)

● General technical parameters

Standard accuracy: ±0.1%

Temperature drift: ±0.015%/°C

Response time: ≤10mS

Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply

Isolation strength: input-output-power supply ≥100MΩ/500VDC

Effect of load resistance variation: ±0.1%/250Ω (for current output)

                   ±0.1% (for voltage output)

Power-on stabilization time: ≤3s

LU-A22 Detection-End (Signal Input) Isolation Safety Barrier (2 In / 2 Out) Selection Guide

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS