Safety Barriers

Product Details · PRODUCT DETAILS

LU-B22 Operation-End (Signal Output) Isolation Safety Barrier (2 In / 2 Out)

The LU-B22 safety barrier accepts two independent DC signals below 20mA or 10V, converts them into isolated standard process signals, and limits hazardous energy from entering the hazardous area through the intrinsically safe terminals. It has two independent input and output channels, each magnetically isolated between input, output and power supply.

  • CategorySafety Barriers
  • Model-
  • Views8286 views
  • Updated2011-11-25
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111

I. Overview

● The LU-B22 safety barrier can be connected to two independent DC signals of less than 20mA or less than 10V.

● Converts DC signals into isolated standard process signals and limits hazardous energy from entering the hazardous location through the intrinsically safe terminals.

● Two independent input and output channels; for each channel, the input, output and power supply are magnetically isolated from one another.

II. Technical parameters

●Input parameters (safe area signals)

■For current input  Input range: 4~20mA

Input resistance: built-in input resistor 50Ω

■For voltage input  Input range: 1~5V, 0~5V, 0~10V

Input resistance: ≥500KΩ

●Output parameters (hazardous area signals)

■For current output  Output range: 4~20mA

Permissible load: ≤750Ω

■For voltage output  Output range: 1~5V

Output impedance: ≤500KΩ

●Intrinsic safety parameters

Explosion-proof marking:       [Exia]ⅡC

Maximum voltage Um:    250V    

Maximum output voltage Uo: 28V

Maximum output current Io: 93mA

Maximum external inductance Lo: 2.4mH

Maximum external capacitance Co: 0.05µF

● Ambient parameters

Power sup ply: 20-30VDC

Ripple factor below 10%P-P, approx. 1W 

Power indicator lamp: green LED, lit when the power is supplied

Operating temperature range: -20~ +60°C

Operating humidity range: 0 ~ 95%RH (non-condensing)

● General technical parameters

Standard accuracy: ±0.1%

Temperature drift: ±0.015%/°C

Response time: ≤10mS

Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply

Isolation strength: input-output-power supply ≥100MΩ/500VDC

Effect of load resistance variation: ±0.1%/250Ω (for current output)

                   ±0.1% (for voltage output)

Power-on stabilization time: ≤3s

LU-B22 Operation-End (Signal Output) Isolation Safety Barrier (2 In / 2 Out) Selection Guide

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS

Related Products

View Related Products

Need technical specifications and a quotation for this product?

Submit your request and our engineers will contact you within one business day.