Safety Barriers
Product Details · PRODUCT DETAILS
LU-B22 Operation-End (Signal Output) Isolation Safety Barrier (2 In / 2 Out)
The LU-B22 safety barrier accepts two independent DC signals below 20mA or 10V, converts them into isolated standard process signals, and limits hazardous energy from entering the hazardous area through the intrinsically safe terminals. It has two independent input and output channels, each magnetically isolated between input, output and power supply.
I. Overview
● The LU-B22 safety barrier can be connected to two independent DC signals of less than 20mA or less than 10V.
● Converts DC signals into isolated standard process signals and limits hazardous energy from entering the hazardous location through the intrinsically safe terminals.
● Two independent input and output channels; for each channel, the input, output and power supply are magnetically isolated from one another.
II. Technical parameters
●Input parameters (safe area signals)
■For current input Input range: 4~20mA
Input resistance: built-in input resistor 50Ω
■For voltage input Input range: 1~5V, 0~5V, 0~10V
Input resistance: ≥500KΩ
●Output parameters (hazardous area signals)
■For current output Output range: 4~20mA
Permissible load: ≤750Ω
■For voltage output Output range: 1~5V
Output impedance: ≤500KΩ
●Intrinsic safety parameters
Explosion-proof marking: [Exia]ⅡC
Maximum voltage Um: 250V
Maximum output voltage Uo: 28V
Maximum output current Io: 93mA
Maximum external inductance Lo: 2.4mH
Maximum external capacitance Co: 0.05µF
● Ambient parameters
Power sup ply: 20-30VDC
Ripple factor below 10%P-P, approx. 1W
Power indicator lamp: green LED, lit when the power is supplied
Operating temperature range: -20~ +60°C
Operating humidity range: 0 ~ 95%RH (non-condensing)
● General technical parameters
Standard accuracy: ±0.1%
Temperature drift: ±0.015%/°C
Response time: ≤10mS
Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply
Isolation strength: input-output-power supply ≥100MΩ/500VDC
Effect of load resistance variation: ±0.1%/250Ω (for current output)
±0.1% (for voltage output)
Power-on stabilization time: ≤3s
LU-B22 Operation-End (Signal Output) Isolation Safety Barrier (2 In / 2 Out) Selection Guide
Click to download the product manual. If the download fails, please contact customer service.
Related Products
Need technical specifications and a quotation for this product?
Submit your request and our engineers will contact you within one business day.