LU-193/190 Series Multi-function Meters

Product Details · PRODUCT DETAILS

LU-193-ASNNN-SDWF Power Monitoring Meter

The LU-193 series intelligent power monitoring meter is a multi-function, high-precision and highly reliable power monitoring device. Its powerful expansion modules can replace a variety of instruments such as transmitters, relays and other function modules at favorable cost performance. As an advanced intelligent digital grid acquisition terminal, it is widely used in power monitoring systems for utilities, industrial and mining enterprises, public facilities and intelligent buildings.

  • CategoryLU-193/190 Series Multi-function Meters
  • Model-
  • Views5965 views
  • Updated2015-05-18
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111

LU-193-ASNNN-SDWFThe LU-193 series smart power monitor is an intelligent power monitoring device with multiple functions, high accuracy and high reliability. Its powerful expansion function modules can replace a variety of instruments such as transmitters, relays and other functional modules, delivering high cost effectiveness. As an advanced intelligent, digital power grid acquisition terminal, the LU-193 series power monitor can be widely used in power monitoring systems of power systems, industrial and mining enterprises, public utilities, intelligent buildings and other facilities.


Terminal No.

Terminal definition

Terminal No.

Pin definition

Terminal 1

Auxiliary power supply wiring terminals of the instrument

1

Chassis ground FG

3

Auxiliary power supply N terminal

5

Auxiliary power supply L terminal

Terminal 2

Voltage signal input and extension energy pulse wiring terminals

6

Energy pulse output EP1-

8

Energy pulse output EP1+

10

Energy pulse output EP2-

12

Energy pulse output EP2+

15

Voltage signal input U0

17

C phase voltage signal input Uc

19

B phase voltage signal input Ub

21

A phase voltage signal input Ua

Terminal 3

 

Current signal input and expansionRS485wiring terminals

22

RS485communication wiring B

23

RS485communication ground

24

RS485communication wiring A

28

C phase current output I3

29

C phase current input I3*

31

B phase current output I2

32

B phase current input I2*

34

A phase current output I1

35

A phase current input I1*

2. Technical Specifications

2.1  Basic Technical Parameters

LU193 basic technical parameters are listed in the table below:

Item

Technical Specification

Measurement accuracy

Voltage: 0.2 class          Current: 0.2 class

Active power: 0.5 class      Reactive power: 0.5 class

Apparent power: 0.5 class      Power factor: 0.5 class

Active energy: 0.5 class        Reactive energy: 1 class

Frequency 0.1 class

Harmonic measurement

2nd to 31st-order voltage and current harmonic components

Wiring mode

Three-phase four-wire; three-phase three-wire; single-phase two-wire.

Frequency range

45~65Hz

Rated input signal

Voltage: 420V        Current: 5A

Burden

Voltage: <0.6VA(420V)   Current: <0.1VA

Overload capability

Voltage: 750V continuous; 1000V 10 s; 1200V 3 s

Current: 2 times rated continuous; 1 times rated for 30 s; 25 times rated for 2 s; 50 times rated for 1 s

Auxiliary power supply

AC: 85~265V  45~65Hz

DC: 100330V

Power consumption

≤2W,4VA

Operating conditions

Temperature: -10~+50°C; Humidity: 20~95% (non-condensing)

Storage conditions

Temperature: -25~+75°C; Humidity: 20~95% (non-condensing)

Dimensions

Basic model: 96mm×96mm×88mm

With expansion module: 96mm×96mm×108mm

Panel cutout

Square: 92mm×92mm

Round: diameter d=100mm

Net weight

0.8 kg

 

 

LU-193-ASNNN-SDWF Power Monitoring Meter User Manual

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS

Related Products

View Related Products

Need technical specifications and a quotation for this product?

Submit your request and our engineers will contact you within one business day.