Products > Industrial Intelligent Instruments > Safety Barrier > LU-B11 (TypeS) barriers

LU-B11 (TypeS) barriers


1.Technical Parameters:
1) main functions and features
● compact and insert-mounting
● output circuit Intrinsic Safety, [Exib]ⅡC if suitably certified.
● May connect with each kind of DC signal which <20mA or <10V,
● Transfer the DC signal to isolated standard process signal, and prevent hazardous energy from the instrinsically safety terminal into the hazardous area.
● With power indicator, Zero & Span adjustment for output signal
● Input, output and power supply are isolated from each other
● Output may with power supply

2)input (safe-area signal)
●  current input:  current: 4~20mA,
input resistance: 100Ω (built-in)
●  voltage input:  voltage: 1~5V,
input resistance: >50 KΩ

    3)  output (hazardous-area signal)
●  current output:  current: 4~20mA,
load resistance: ≤750Ω
●  voltage output:  voltage: 1~5V,
                 resistance: 250Ω (built-in)
load resistance: ≥10 KΩ

  4) Intrinsic safety:
● Explosion-proof: [Exib]ⅡC
● max. voltage Um: 242V
● max. output voltage Uo: 28V
● max. output current Io: 118mA
● max. external inductance Lo: 1.5mH
● max. external Capacity Co: 0.083μF

5) environmental parameters:
● power supply: DC24V±10%, current consumption 1W when aftereffect Wpp < 10%
● temperature for operating: 0℃ ~ +50 ℃
● humidity: 0~90%RH (none congeal)

   2. performance index (to full span)
● standard accuracy: ±0.1% FS
● temperature drift: ±0.015%/℃
● response time: ≤0.5s (0→90%)
● power voltage affect: ±0.1%/permitted voltage range
● insulated resistance:
Input, output and power supply are isolated from each other ≥100 MΩ/DC 500V
● isolation intensity: input-output-power supply-ground:
DC 1500V/1 minute (DC power)
AC 1500V/1 minute (AC power)
● load resistance affect: ±0.1%/500Ω (when current output)
● settling time: ≤3s

   3. construction and dimension
● structure: compact, insert-mounting
● connection: 3mm connection terminal
● terminal screw material: nickel plating around surface of iron
(screw arrowed wrest<0.8N•m)
● shell material: burn-bear colophony
● isolation: channel isolation (input,output and power supply are isolated from each othe)
● zero adjustments-range: -5 ~ +5%
● span adjustments-range: 95~105%
● power indicate light: green LED, light on when power supply
● mounting: DIN rail
● outline dimension (W×H×D): 25×80×80mm
● net weight: app. 150 g
 

After-sale service Pre sales consultation

Login  |  Register  Please login to ask question!




  • LU-BK1 (TypeS) barriers

  • LU-AK1 (TypeS) barriers