Products > Industrial Intelligent Instruments > Pressure Transmitter > LU-CHP electric capacity high static-pressure differential-pressure transmitter

LU-CHP electric capacity high static-pressure differential-pressure transmitter

1.technical performance

·to subject: liquid, gas or vapour

·range ability: 

LU-CHPS-7400

0-6-36kpa

LU-CHPS-8400

LU-CHPS-9400

LU-CHPS-7500

0-30-180kpa

LU-CHPS-8500

LU-CHPS-9500

·output: 4-20mA DC

·power: 24VDC, it may be 12VDC if non-load, max. is 45VDC

·positive & negative transfer: up and low may not exceed the range limit after positive & negative transfer, whatever the output is.

Max. positive transfer: 500% of the min. span.

Max. negative transfer: 600% of the min. span.

·Temperature:

temperature of operating for amplifier: -25 +90

temperature of operating for sensor:  -40 +104

·Relative humidity: 0~100%

·Sensor capacity changes: <0.16cm3

·Indicate meter (field): scale gauge length: 30mm,

grade: 2.5

·Isolating explosion: ds BT5,   Intrinsically-safety: ia CT5

·Span & Zero: external continually adjusted

·Static-pressure and Over-pressure limit:

Max. operating pressure: 32Mpa

Max. safe pressure: 32Mpa

Single-side Max. pressure: 32Mpa

Flange bear pressure: 60Mpa

·Static-pressure affect:

zero error: <±2% of max. range, when operating pressure is 32Mpa

range error: is a system error, can be calibrated.

·Damp: continually adjusted when time constant is between 0.2~1.67 seconds.

·Settling time: 2s,

 

2. performance index (note: test under the condition of none shift, max. range status of sensor, 316L stainless isolating diaphragm and other standard condition)

·Accuracy: ±0.25% of the span, including the synthesize errors of linear,     change-difference and repeat.

·Stability: ±0.25% of max. range (12 months)

·Temperature affect:

zero error:±0.5% / 55,  zero & range errors:±1.0% / 55, when max. range;

zero error:±3.0% / 55,  zero & range errors:±3.5% / 55, when min. range;

·Over-pressure affect: ±1%~±5% of max. range (according to permitted over-loads for different ranges)

·vibration affect: ±0.05% / g of the max. range, when 200Hz, any axis up.

·Power affect: <0.005%/V of output range

·Load affect: none affect when voltage >12VDC input to the transmitter.

·Mounting position affect: may cause zero error max. 0.24Kpa, but can be calibrated,   none affect for range

 

3. structure index:

·Structure material: diaphragm: 316 stainless steel, hastelloy C, Monel alloy, Tantalum;

                 O ring: Fluorin rubber;

Flange & bolt: 316 stainless steel;

Fill oil: silicon oil;

Electric shell: low-Cu & aluminum alloy

Plating of electric shell: toast lacquer of amido, formyl, ethene & colophony;

·pressure-lead connector:

flange NPT 1/4 (taper pipe screw thread), (this is the transmitter flange connection);

connection head screw thread NPT 1/2 (taper pipe screw thread), (selected); 

·electric parts connector:

down-lead conduit NPT 1/2 line-through hole;

·net weight: 2.4kg (exclude the selected parts)

After-sale service Pre sales consultation

Login  |  Register  Please login to ask question!




  • LU-L proliferate silicon liquid-level transmitter

  • LU-K proliferate silicon pressure transmitter

  • LU-CDP/GP remote flange diaphragm differential-pressure transmitter