产品中心 > Industrial Intelligent Instruments > Industrial Display Controller > Memory Type Digital Controller LU-921M

Memory Type Digital Controller LU-921M

 1. Brief Introduction

 
LU-921M memory type two channels controller has two independent channels,the input of them maybe different.The fast and accurate non-linear algorithm ensures the accuracy of digitized sampling.
 
It can achieve the function of differential algorithm alarm or transform through the parameters setting of alarm source and transform source.
 
 
2. Main Technical Parameters
 
●Accuracy: ±(0.2%F.S.+1)digit
●Resolution: 1℃ , 0.1℃
●Control method: ON/OFF
●Display: double 4-bit LED +light pillar
●Input type: 
T.C: S(-50~1768℃),R(-50~1768℃),B(250~1820℃), 
K(-200~1372℃),N(-200~1300℃),E(-200~1000℃),
J(-200~1200℃), T(-200~400℃).
RTD:Pt100(-200~800℃),Cu50(-50~150℃),Cu100(-50~150℃)
standard mV signal: 0-100mV
standard resister signal: 0-500 ohm
standard voltage signal: 0-10V,0-5V,1-5V,self-defined 0-10V
standard current signal: 4-20mA,0-10mA,self-defined 0-20mA
●Output modules:
J8:relay output (250VAC/3A,normally open+normally close)
J9:relay output (250VAC/0.8A,normally open+normally close)
J7:double relay output (250VAC/0.8A,normally open)
G1:SSR trigger output (12V/30mA)
I5: control / transform current output 
U5: control / transform voltage output
V6/V7: 12V/24V 50mA sensor power supply
S2: RS232 communication
S4: RS485 communication
M1:2nd sampling input (T.C,RTD,0-5V,1-5V)
M3:2nd sampling input (T.C,RTD,0-10mA,4-20mA)
●T.C cold Junction compensation error: ±1℃
●T.C.break or over range: display Sb
●Sampling period: 0.5 second
●Power voltage: 85~265VAC
●Power consumption: <4W
 